When do fixings affect the corrected Uc value?
Fasteners passing through EPS can increase heat flow through an insulated wall. Their effect depends on the construction, the installation method and their number. Therefore, the U-value for the layers alone is not always the final Uc result. Thermal data for the fixings and a layout plan are needed. Saving on the number of fasteners is not a way to improve insulation performance. A fixing creates a local disturbance in the homogeneous insulation layer. Heat can flow differently around it than through the EPS field alone. The effect of a single element may be small, but there are many of them on a façade. The better insulated the undisturbed wall is, the greater the relative share a given addition from fixings can have.