Core thermal conductivity and panel U-value: checking a quotation for an industrial wall

PIR insulation

At a glance

The hall design specifies a required U-value, but the quote for sandwich panels only states the lambda of the PIR core. These figures cannot be compared directly. The first relates to heat transfer through a defined element, the second describes the core material. To assess the quote, find the U-value in the manufacturer's documentation for the proposed wall model and its thickness. Then establish whether the design requires a value for the panel alone or for the entire wall including details. We show how to prepare such a comparison and when to leave an item open rather than treat it as compliant.

Metal-faced panel sample with an exposed insulation core and two facing samples

Two figures, two different things being assessed

The unit helps you catch a mistake: λ is given in W/(m·K), U in W/(m²·K). If the same symbol and the same unit do not appear on both sides of the comparison, hold off on your assessment. A small figure does not yet mean that the project requirement has been met.

First establish the model stated in the quote

Ask for the full designation of the panel, not just a phrase such as “PIR 100”. A single commercial family may include products for walls and for roofs. For a quote for a hall façade, include the datasheet for the wall version stating the joint type.

Check what the dimension on the cross-section drawing refers to. The core thickness and the maximum height of the profiled element need not mean the same thing. If two figures are given in the roof specification, do not carry either of them over to the wall selection without checking the legend.

Find the correct row in the U-value table

In the datasheet for the selected type, read off the thermal transmittance value from the row that applies to the thickness you are ordering. Note the table number and catalogue edition alongside it. If the supplier changes the model in a later version of the offer, it will be immediately clear which reading needs to be repeated.

Also read the notes below the table. If the manufacturer specifies how a joint is to be taken into account or the scope of the stated value, keep this information together with the result. The absence of such a note does not confirm that all joints in the finished façade have been included.

What have we actually calculated from lambda?

A purely arithmetic example: for a homogeneous core 0.100 m thick and an assumed λ = 0.025 W/(m·K), the thickness divided by lambda is 4.00 m²·K/W. This is the thermal resistance of the model core layer, not a test result or a declaration for the panel on offer.

Inverting this result gives 0.25 W/(m²·K). The unit already looks like a U-value, but the model still covers only the core. Do not enter this figure in the 'panel U-value according to manufacturer' field. Leave that for the value from the documentation for the specific product.

Where does the panel data end?

At the plinth, corner and door surround, the panel meets another component. Draw the boundary between the panel field and these details. This makes the question to the designer specific: which junctions were checked separately, and in which calculation?

Do not try to correct the catalogue value with your own fixed percentage 'for thermal bridges'. You then do not know what the manufacturer has already included and what you are counting twice. In the tender comparison, show the panel value and keep the assessment of the designed details as a separate item.

Close the comparison before ordering

A complete note can have one line per variant: product designation, wall application, thickness, U-value with the table number, and the requirement it was compared against. Enter the core lambda in a separate column where it is needed for further analysis.

If the offer stops at the name of the foam and its lambda, write “no U-value for the offered panel” and ask for the datasheet. This gives a more precise assessment result than rejecting a good product or accepting it on the basis of a figure describing a different parameter.

7 branches. Materials closer to your project.

Izoprofil.eu map of seven branches offering sandwich panels, PIR boards and sheet metal
  • SEROCK — Dzierżenin 34 E [mapa]
  • BŁONIE — ul. Sochaczewska 138A [mapa]
  • RADOM — ul. Grobickiego 8 [mapa]
  • ŁÓDŹ — Natolin 8 [mapa]
  • OLSZTYN — Barczewo, ul. Prosta 9 [mapa]
  • WROCŁAW — ul. Jerzmanowska 10C [mapa]
  • GORZÓW WLKP. — ul. Zielona 33/34 [mapa]

Check prices and availability: +48 500 409 109

Free quote

Materials for your project